Inspection
Inspection Details
Equipment ID
9330
9330
Inspection Date
9/3/2019
9/3/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
d24552d0-b76c-42c5-b2ff-bc6a207063f3
d24552d0-b76c-42c5-b2ff-bc6a207063f3
Location
Warehouse Building
3431 SCHOOL ST, SAINT LOUIS, MO
Phone: (314) 633-9103
3431 SCHOOL ST, SAINT LOUIS, MO
Phone: (314) 633-9103
Owner
Attn: UNK
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
Billing
Attn: Cindy Williams
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: cindy@advancedelevator-stl.com
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: cindy@advancedelevator-stl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 1/20/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | Yes | The lobby doors shall remained locked while the car is away from the landing. Elevator Red Tagged. | 10/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car top lighting shall be operational. | 1/20/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 1/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car top lighting shall be operational. | 1/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 11/25/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove water and debris from the pit. | 11/25/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | The freight elevator car shall have a solid enclosure, there is a substantial gap between the enclosure and the light fixture which shall be constructed. The construction shall be either perforated or lattice work and shall reject a ball one and one-half inches (1 1/2") in diameter. | 11/25/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect freight handlers. | 11/25/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | The freight car enclosure shall have loading class plates, and a “No Passengers” sign conspicuously posted. Letters shall not be less than one-half inch (1/2") high. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2004. | 11/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 11/25/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 11/25/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Cab has excessive gaps in the ceiling, enclose. | 11/25/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door is to be self closing and self locking. | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 1/9/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe and convenient access to the elevator machine room, fold up ladder is being used. | 1/9/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase I instructions,in the lobby near the f/f switch. | 1/9/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove scavenger unit from the pit. | 1/9/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the scavenger return line. | 1/9/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Cab walls have been hit, pushed away from cab. Straighten panels (as best as possible) reattach to cab floor. | 1/9/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced. 2nd notice | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing "Loading Class" sign in car. 2nd notice | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room. 2nd notice | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe access to machine room, fold up ladder is not acceptable. 2n notice | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self locking & self closing. 2nd notice | 4/10/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Light bulbs in car shall be guarded. 2nd notice | 4/10/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)4 | No | No | Car enclosure has openings around front light fixture that need to be closed up. 2nd notice | 4/10/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Cab panels in rear of car have been damaged and broken loose from cab floor, need to re-fasten to floor. 2nd notice | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit which is to only be used temporarily that must be removed along with oil return line to tank. Replace with proper container t collect and measure oil loss. 2nd notice, | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged rubber astragal on bottom floor door | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | Yes | Machine room door shall be self locking & self closing. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | Yes | Yes | Provide safe access to machine room, fold up ladder is not acceptable. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | Yes | A written copy of the MCP shall be kept in the machine room. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | Yes | Fire extinguisher in machine room is expired, have serviced or replaced. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)4 | Yes | Yes | Car enclosure has openings around front light fixture that need to be closed up. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | Yes | Yes | Cab panels in rear of car have been damaged and broken loose from cab floor, need to re-fasten to floor. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | Yes | Replace damaged rubber astragal on bottom floor door. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | Yes | Yes | Light bulbs in car shall be guarded. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | Yes | A copy of the current state operating certificate shall be displayed in the machine room. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | Yes | Unit has oil recovery pump in pit which is to only be used temporarily that must be removed along with oil return line to tank. Replace with proper container to collect and measure oil loss. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | Yes | Yes | Need to replace missing "Loading Class" sign in car. Red tag and reinspection required. | 11/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | Yes | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | Yes | Fire extinguisher in machine room is expired, have serviced or replaced. | 1/9/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | Yes | Yes | Need to replace missing "Loading Class" sign in car. | 1/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged rubber astragal on bottom floor door. | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit which is to only be used temporarily that must be removed along with oil return line to tank. Replace with proper container to collect and measure oil loss. | 4/10/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Red Tag remains in place by state elevator inspection department all recommendations must be cleared to remove a red tag. | 1/9/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | All means of access to the elevator machine room shall be of a permanent nature and shall be constructed and maintained in a clear and unobstructed manner. A folding ladder is not permanent. |