Inspection
Inspection Details
Equipment ID
1141
1141
Inspection Date
9/5/2019
9/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Douglas Gildehaus
Douglas Gildehaus
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
6d1cc1a6-c45b-482e-bb65-526100b9f521
6d1cc1a6-c45b-482e-bb65-526100b9f521
Location
Metropolitan Place
10296 BIG BEND RD, SAINT LOUIS, MO
Phone: (314) 605-8530
10296 BIG BEND RD, SAINT LOUIS, MO
Phone: (314) 605-8530
Owner
Attn: Metropolitan Urological Properties, LLC
Metropolitan Urological Properties, LLC
10296 BIG BEND RD, SAINT LOUIS, MO 63122
Phone: (000) 000-0000
Metropolitan Urological Properties, LLC
10296 BIG BEND RD, SAINT LOUIS, MO 63122
Phone: (000) 000-0000
Billing
Attn: Metropolitan Urological Properties, LLC
Metropolitan Urological Properties, LLC
215 DUNN RD, FLORISSANT, MO 63031
Phone: (314) 315-9905
Email: kims@metrourology.net
Metropolitan Urological Properties, LLC
215 DUNN RD, FLORISSANT, MO 63031
Phone: (314) 315-9905
Email: kims@metrourology.net
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative | 10/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Twin post Jacks making excessive noise in the down direction. Determine cause and repair. | 10/11/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit stopped working. Provide Relief pressure, record. Check packing for leaks. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of emergency lights and bell. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of phone. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of Phase I operations, record results. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of Phase II operations, record results. | 9/12/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in the pit is due for testing, provide. | 8/19/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperable | 12/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to perform stop ring pressure test | 12/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone. | 12/5/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit to work properly. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Need to repair door closed button or replace same |