Inspection
Inspection Details
Equipment ID
2812
2812
Inspection Date
10/2/2019
10/2/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
11
11
External ID
82c5267d-2bf5-410f-9a85-0f29580b4470
82c5267d-2bf5-410f-9a85-0f29580b4470
Location
SSM-St. Joseph Health Center
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
Owner
Attn: Marie O'Donnell
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301
Phone: (314) 989-6134
Email: marie.odonnell@ssmhealth.com
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301
Phone: (314) 989-6134
Email: marie.odonnell@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Provide & install crosshead data plate with manufacturer name, date of installation, speed & rated capacity stamped on it. | 10/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Door closers at top and bottom floors are not working | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair / replace ventilation fan in car | 10/14/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working on auxiliary power. Re-inspection required | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has had 9 inches of oil / water, has possible black mold. Pit needs to be cleaned ad mold abated. Recommend after cleaning remove any rust from equipment and apply rust inhibitor to prevent any further damage to equipment | 1/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair existing lighting in machine room and provide for additional lighting if needed to provide required 10 fc minimum illumination at floor in front of controller | 1/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Need to install cover on 4x4 electrical box in corner by disconnect switches and enclose all exposed wiring. | 1/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace leaking Victaulic fittings as needed in pit and machine room | 1/2/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | Yes | OSV failed testing, needs repaired. Red-tagged and removed from service. Re-inspection required | 1/2/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking | 1/2/2026 |