Inspection
Inspection Details
Equipment ID
5519
5519
Inspection Date
10/7/2019
10/7/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Carl Switzer
Carl Switzer
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
e3046cbf-d21d-4933-9099-c1181b4c1781
e3046cbf-d21d-4933-9099-c1181b4c1781
Location
Murphy Manor
128 WALL ST, JOPLIN, MO
Phone: (417) 624-4514
128 WALL ST, JOPLIN, MO
Phone: (417) 624-4514
Owner
Joplin Housing Authority
1834 W 24TH ST, JOPLIN, MO 64804-1511
1834 W 24TH ST, JOPLIN, MO 64804-1511
Billing
Attn: Joplin Housing Authority
1834 W 24TH ST, JOPLIN, MO 64804-1511
1834 W 24TH ST, JOPLIN, MO 64804-1511
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | 1.18 door restrictor needs repaired | 10/9/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | 8.6.4.13.1(l) door restrictor needs repaired | 10/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | temporary under construction | 10/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Car Door restrictor shall work. (less than 4" opening) (REINSPECTION WITHIN 30 DAYS) | 2/26/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm and light shall work with power loss. | 10/22/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | No | No | Hall phase 1 switch shall be FEOK1 and Bezel shall be “reset,off,on” | 10/22/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly | 9/15/2022 |