Inspection
Inspection Details
Equipment ID
3239
3239
Inspection Date
6/23/2017
6/23/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
Location
Research Bldg
Bldg 19, St. Louis, MO
Phone: (314) 516-6311
Bldg 19, St. Louis, MO
Phone: (314) 516-6311
Owner
UMSL
One University Blvd, St. Louis, MO 63121
One University Blvd, St. Louis, MO 63121
Billing
Attn: UMSL- MSC North Garage
One University Blvd, , MO 63121
One University Blvd, , MO 63121
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light in car doesn't work | 5/21/2026 |
| conversion | conversion | n/a | No | No | Remove water and clean pit | 5/21/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase I fire service - Car returns to wrong floor | 12/19/2019 |
| conversion | conversion | n/a | No | No | Door restrictor doesn't work | 5/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit | 5/21/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Phone line dead to controller | 1/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/21/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. There is standing water in the pit. | 5/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light does not illuminate | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone fails to establish two-way communication. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust the car door clutch or replace the rail slide guides so the the clutch is not striking the door rollers at every floor |