Inspection
Inspection Details
Equipment ID
19004
19004
Inspection Date
4/11/2018
4/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
St. Louis Busch Stadium
700 Clark St, St. Louis, MO
Phone: (314) 345-9404
700 Clark St, St. Louis, MO
Phone: (314) 345-9404
Owner
St. Louis Cardinals LLC
700 Clark St, St. Louis, MO 63102
700 Clark St, St. Louis, MO 63102
Billing
Attn: St. Louis Cardinals LLC
700 Clark St, , MO 63102
700 Clark St, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace step chain switches. | 1/7/2019 |
| conversion | conversion | n/a | No | No | Install top and bottom inner deck cards | 1/7/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Comb impact guides are rusted and need to be tested to insure proper impact calibration. | 2/21/2019 |
| conversion | conversion | n/a | No | No | Replace missing bottom right and top right and left end cap weather guard. | 1/7/2019 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.5 | No | No | Replace broken step demarcation strip. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 1008.2r | No | No | Comb impact switches are not working. Repair and Reinspect. Escalator red-tagged. | 3/29/2023 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Clean escalator truss space. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.6 - Caution Signs | 805.9 | No | No | Upper left guard needs a caution sign. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.16 - Ceiling intersection guards | 802.3g | No | No | Replace wrong ceiling intersection guards with correct ones. | 7/12/2023 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Entire unit needs a clean down. | 7/12/2023 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 1206.6 | No | No | Step demarcation strip is broken on a couple of steps | 6/28/2022 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Perform Annual Clean Down truss top and bottom end | 8/26/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Record maintenance, call backs, repairs, and testing in MCP and place sticker on controller where MCP is located | 8/26/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(d) | No | No | Record Step/skirt Indexing Graph for 2025 in MCP | 8/26/2025 |
| A17.1-1996 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 802.3e | No | No | Replace missing screws on deck panel trim at upper end top curve | 8/26/2025 |