Inspection
Inspection Details
Equipment ID
20652
20652
Inspection Date
10/1/2019
10/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
c601f6fd-5e48-465c-9490-83e43f50b724
c601f6fd-5e48-465c-9490-83e43f50b724
Location
Stifel Theatre
1400 MARKET ST, SAINT LOUIS, MO
Phone: (314) 499-7701
1400 MARKET ST, SAINT LOUIS, MO
Phone: (314) 499-7701
Owner
Attn: Adrian Silverstein
Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Scottrade Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Billing
Attn: Scottrade Center
Stifel Theatre
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Stifel Theatre
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 499-7701
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Replace missing conduit in bottom of pit. | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction, needs to be replaced. Re-inspection required | 9/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in the machine room is expired, have serviced or replaced | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform no load testing of car safeties after safety drum rope is replaced with proper material. Re-inspection required | 9/15/2023 |
| A17.1-2016 : Elevators | 11.11 - Emergency Brake | 2.19.3 | Yes | No | Emergency brake failed to stop car within allowable distance (48") when performing un-intended movement test, repair & re-test. Re-inspection required | 9/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the emergency power selector switch. This is found next door in the security office. | 10/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct speed on the cross head data plate. | 10/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Numerous ledges in the hoistway exceeding code required 4”, repair as needed. | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 10/1/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 4/10/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | Install crosshead data plate with correct speed (200 fpm) | 4/10/2026 |