Inspection
Inspection Details
Equipment ID
6180
6180
Inspection Date
9/16/2019
9/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
961902a8-6809-4073-b774-11df0b4f7bf6
961902a8-6809-4073-b774-11df0b4f7bf6
Location
Willert Home Products
4128 PARK AVE, SAINT LOUIS, MO
Phone: (314) 772-2822
4128 PARK AVE, SAINT LOUIS, MO
Phone: (314) 772-2822
Owner
Willert Home Products
4044 PARK AVE, SAINT LOUIS, MO 63110-2320
4044 PARK AVE, SAINT LOUIS, MO 63110-2320
Billing
Attn: Willert Home Products
4044 PARK AVE, SAINT LOUIS, MO 63110-2320
4044 PARK AVE, SAINT LOUIS, MO 63110-2320
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired and shall be replaced or re-certified. | 9/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 6/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired and shall be replaced or re-certified. | 9/18/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 9/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is expired and shall be replaced or re-certified. | 9/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. This unit has no MCP in place. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The fire extinguisher is expired. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than ten foot-candles at floor level. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') in height and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. Note: The machine and controller is in an open area above the hoistway without a door, access is unrestricted from the elevator lobby via a wooden ladder and does not meet these requirements. The door controls are also unrestricted, and located at the top floor lobby and not in a separate room or space. Customer may need to apply for a variance. |