Inspection
Inspection Details
Equipment ID
10041
10041
Inspection Date
9/16/2019
9/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
c30aec9a-f45d-40ee-bbe7-a3c04af05f89
c30aec9a-f45d-40ee-bbe7-a3c04af05f89
Location
University Club Tower
1034 S BRENTWOOD BLVD # PH1A, RICHMOND HEIGHTS, MO
Phone: (314) 727-6664
1034 S BRENTWOOD BLVD # PH1A, RICHMOND HEIGHTS, MO
Phone: (314) 727-6664
Owner
Attn: CF Clayton Office 2 LP
CF Clayton Office 2 LP
1034 S BRENTWOOD BLVD, RICHMOND HEIGHTS, MO 63117
Phone: (000) 000-0000
Email: Choltzman@stlcre.com
CF Clayton Office 2 LP
1034 S BRENTWOOD BLVD, RICHMOND HEIGHTS, MO 63117
Phone: (000) 000-0000
Email: Choltzman@stlcre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Hoist ropes are rouged and approaching minimum diameter. The hoist ropes shall be replaced and re-inspected within 90 days. | 6/6/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 8/18/2026 |
| A17.1-1996 : Elevators | 3.27 - Crosshead data plate | 1001.2(c)(11) | No | No | A rope data tag is required. | 8/18/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency power shall be tested. | 9/10/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to simulate the fire alarm initiating devices for phase 1 recall. | 9/10/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate in the elevator machine room. | 8/18/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance documents (MCP). | 8/18/2026 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | The counterweight is slightly compressing the buffer when the car is at the top floor. Provide code compliant counterweight runby. | 9/10/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested to complete the annual inspection. | 9/27/2021 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | Car safeties are not operating properly. Could not get safeties to set. Elevator Red Tagged. | 9/27/2021 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | Car safeties are not operating properly. Could not get safeties to set. Elevator Red Tagged. | 6/8/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be tested and shall be code compliant. | 9/19/2023 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | Hoisway ropes need to be shortened. | 9/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested to complete the annual inspection. | 9/19/2023 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 107.1b | Yes | No | Hoistway ropes need to be shortened. | 12/5/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested as required. | 8/13/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 8/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The standby power selector switch and light shall be removed or marked "for future use" - the building is not equipped with emergency power for the elevators. | 8/18/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 8/13/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 8/18/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Yes | No | Fire service shall be tested. |