Inspection
Inspection Details
Equipment ID
11169
11169
Inspection Date
4/27/2018
4/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
25F/28R
25F/28R
External ID
Location
Pierre Laclede Center-
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
Owner
CBRE
7733 Forsyth Blvd, Suite 295, Clayton, MO 63105
7733 Forsyth Blvd, Suite 295, Clayton, MO 63105
Billing
Attn: CBRE
7733 Forsyth Blvd, Ste 295, , MO 63105
7733 Forsyth Blvd, Ste 295, , MO 63105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Schedule a full lad test of the emergency power system on elevators 1-8. | 4/23/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency power shall be tested with 125% of capacity. | 7/28/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. | 4/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car front door restrictor shall work at all floors. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 211.9 | No | No | COP shall display unit identifier (Elevator #7). | 3/26/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 3/26/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Missing pickup flags on inside of hoistway doors on floors 7 & 23. | 3/24/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired State operating certificate in the machine room. |