Inspection
Inspection Details
Equipment ID
6085
6085
Inspection Date
3/28/2018
3/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Arch Hotel Project Owner LLC
4th & Chestnut, St. Louis, MO
Phone: (314) 655-1234
4th & Chestnut, St. Louis, MO
Phone: (314) 655-1234
Owner
Arch Hotel Project Owner LLC
4th & Chestnut, St. Louis, MO 63102
4th & Chestnut, St. Louis, MO 63102
Billing
Attn: Arch Hotel Project Owner LLC
4th & Chestnut, , MO 63102
4th & Chestnut, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Bottom demarcation lights don't work | 5/1/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(D) | No | No | Replace broken step tread. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Written maintenance control program shall be provided on-site for each elevator. | 12/19/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Lower escalator brake torque is only 64 ft lbs. Minimum is 125 ft lbs. Replace escalator brake. Escalator removed from service & red tagged. Re-inspection required before use | 2/22/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | No | No | Broken comb plate at the bottom shall be replaced | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace broken step tread. Re-inspection required | 3/29/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Unit needs complete cleandown | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | Yes | Most, if not all, step treads have damaged fins on treads, causing sharp edges and excessive gaps between fins. Red-tagged, Re-inspection required | 10/2/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | Yes | Bottom brake torque is below minimum. Red-tagged, Re-inspection required | 10/2/2024 |
| A17.1-2016 : Elevators | 9.16 - Ceiling intersection guards | 8.6.8.9 | No | No | Replace anti climbing barricade on outer decking between units at lower end | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 Escalator Entrance and Egress Ends | No | No | Walkoff plate at egress end had missing/broken support braces underneath, need to be replaced | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/29/2024 |