Inspection
Inspection Details
Equipment ID
6505
6505
Inspection Date
4/9/2018
4/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
390
390
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
24
24
External ID
6505
6505
Location
Extended Stay America
5555 Veterans Memorial Pkwy, St. Peters, MO
Phone: (636) 976-2800
5555 Veterans Memorial Pkwy, St. Peters, MO
Phone: (636) 976-2800
Owner
ESA Management c/o Lerch Bates
4201 Northview Drive, Ste 314, Bowie, MD 20716
4201 Northview Drive, Ste 314, Bowie, MD 20716
Billing
Attn: ESA Management c/o Lerch Bates
4201 Northview Drive, Ste 314, , MD 20716
4201 Northview Drive, Ste 314, , MD 20716
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Alarm bell not working | 4/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller | 3/9/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 4/16/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Make arrangements to test lobby smoke detectors--failed to simulate smoke detectors | 4/16/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | 2.8.2.1 - A duplex GFCI receptable shall be provided in the machine room. | 4/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car telephone shall be operational. The phone has a dial tone, but it appears to be restricted and will not dial out. The phone monitor has been tested and meets requirements. | 4/23/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | 2.2.5.1 - The pit lighting shall provide an illumination of not less than 10 fc at the pit floor. New pit lighting was installed, but it does not meet illumination requirements. | 4/23/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | 2.8.2.1 - Feeder locations for the main and lighting branch circuits shall be marked on the main and lighting disconnects. | 4/23/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of section 8.7. | 4/23/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | 2.27.3.2.1(c) - The smoke detector in the overhead shall be removed. There are no sprinklers in the hoistway. | 4/23/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not programmed to dial out. | 12/12/2025 |