Inspection
Inspection Details
Equipment ID
10139
10139
Inspection Date
4/12/2018
4/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
35
35
External ID
Location
Argyle Parking Garage
225 N Euclid Ave, St. Louis, MO
Phone: (314) 589-6023
225 N Euclid Ave, St. Louis, MO
Phone: (314) 589-6023
Owner
St. Louis City Treasurer
133 S 11th St, Ste 520, St. Louis, MO 63102
133 S 11th St, Ste 520, St. Louis, MO 63102
Billing
Attn: Kiel Parking Facility
133 S 11th St, Ste 530, , MO 63102
133 S 11th St, Ste 530, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Front door torque needs to be adjusted below 30 pounds | 11/20/2019 |
| conversion | conversion | n/a | No | No | Fire extinguisher needs to be serviced | 11/20/2019 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Securely fasten car top handrail at all points. | 11/20/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 3/14/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work correctly. | 8/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/14/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing in-car capacity plate. | |
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 204.1e | No | No | Top emergency exit shall be properly secured. The latches are broken. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing elevator capacity signage in elevator cab | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing elevator capacity signage in elevator cab |