Inspection
Inspection Details
Equipment ID
12670
12670
Inspection Date
10/7/2019
10/7/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
e69d6d2a-864c-4bd5-bb47-d4709a74dd94
e69d6d2a-864c-4bd5-bb47-d4709a74dd94
Location
West County Center
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
Owner
Attn: Mike Baker
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair Demarcation lights | 10/7/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Complete Annual Test-step indecing-within 30 days | 7/30/2018 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 806.2 | No | No | Upper and lower demarcation lights are not working. Repair | 10/7/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Step chain clearances do not meet requirement. RED TAGGED | 10/7/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.11 | No | No | Entire truss needs to be cleaned out. | 10/7/2019 |
| A17.1-1996 : Escalators | 8.2 - Stop switch | 805.3e | No | No | Upper level stop switch buzzer is not working. | 10/7/2019 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 1009.2d | No | No | Demarcation lights not working on both top and bottom. | 12/21/2020 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Left handrail needs to be replaced. | 12/21/2020 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | Stop switch buzzer on top not working. | 12/21/2020 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation light not working at bottom egress | 11/25/2019 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Lower demarcation light is out | 12/7/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Step indexing & comb plate impact devices need testing. Re-inspection required | 3/24/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Left handrail has a crack in it creating a pinching hazard. Replace handrail | 11/12/2025 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.8 | No | No | Clean down escalator truss | 8/10/2026 |