Inspection
Inspection Details
Equipment ID
7115
7115
Inspection Date
10/23/2019
10/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
83204eeb-b07a-4e48-b5c2-d514b38051e1
83204eeb-b07a-4e48-b5c2-d514b38051e1
Location
St. Louis Science Center
5050 OAKLAND AVE, SAINT LOUIS, MO
Phone: (314) 533-3009
5050 OAKLAND AVE, SAINT LOUIS, MO
Phone: (314) 533-3009
Owner
Attn: Ron
St. Louis Science Center
5050 OAKLAND AVE, SAINT LOUIS, MO 63110
Phone: (314) 533-8009
Email: ron.staetter@slsc.org
St. Louis Science Center
5050 OAKLAND AVE, SAINT LOUIS, MO 63110
Phone: (314) 533-8009
Email: ron.staetter@slsc.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)2 | Repair torn Astrical on front car gate | 2/25/2020 | ||
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | x | Repair Fire Stop on top of front lower level hatch door southside | 2/18/2020 | |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Repair emergency light in car | 2/18/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Need a maintenance control program on site posted on controller | 12/15/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Need testing procedures in the MCP on or before January 1, 2022 | 2/9/2024 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace missing strap on 1st floor hatch door | 12/12/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair rear hatch door operation | 12/12/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 12/12/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 12/12/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Repair rear hatch door operation | 12/12/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Replace missing strap on 1st floor front hatch door | 12/12/2025 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Replace missing strap on tghe 1st floor hoistway door | 12/12/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 12/12/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Repair Phone In Car. | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace Missing Strap on Front First Floor Hatch Door | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace Missing Strap On Rear Car Gate | |||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Perform Monthly Fire Service test and Document on Log Posted in Machine room | |||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Provide Maint. Control Program. | |||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post Current State Certificate |