Inspection
Inspection Details
Equipment ID
2996
2996
Inspection Date
10/1/2019
10/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
c29b9d04-5359-4f63-929f-e9825c1ef406
c29b9d04-5359-4f63-929f-e9825c1ef406
Location
Byron DuVall
2211 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 776-7100
2211 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 776-7100
Owner
Attn: Byron DuVall
Byron DuVall
2211 OLIVE ST, SAINT LOUIS, MO 63103
Phone: (314) 776-7100
Byron DuVall
2211 OLIVE ST, SAINT LOUIS, MO 63103
Phone: (314) 776-7100
Billing
Attn: Byron DuVall
Byron DuVall
2211 OLIVE ST, SAINT LOUIS, MO 63103
Phone: (314) 776-7100
Byron DuVall
2211 OLIVE ST, SAINT LOUIS, MO 63103
Phone: (314) 776-7100
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove the exposed wires in the elevator hoistway. | 10/12/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | There are some exposed electrical wires inside the hoistway. The exposed wires shall be enclosed in conduit. | 10/12/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 10/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 8/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | When tested on battery power, the bell and emergency light did not work. The alarm bell and emergency light shall be operational on auxiliary power. | 6/14/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/28/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 8/31/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate is expired. | 9/20/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. Note: Strike plate is missing. | 9/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 9/20/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 4 x4 electrical box in machine room needs to have wiring inside box and cover installed. There are two boxes. | 9/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Pit machine space door shall be self-closing and self-locking. | 9/20/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace electrical box covers on car top. | 9/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/9/2025 |