Inspection
Inspection Details
Equipment ID
19085
19085
Inspection Date
10/1/2019
10/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
79015b82-71e4-4c0d-be4b-5b7513348ab1
79015b82-71e4-4c0d-be4b-5b7513348ab1
Location
Monkey Building
1426 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (636) 447-5557
1426 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (636) 447-5557
Owner
1426 Master Tenant LLC
519 WOODMERE XING, SAINT CHARLES, MO 63303-0717
519 WOODMERE XING, SAINT CHARLES, MO 63303-0717
Billing
Attn: 1426 Master Tenant LLC
519 WOODMERE XING, SAINT CHARLES, MO 63303-0717
519 WOODMERE XING, SAINT CHARLES, MO 63303-0717
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | The car top light shall be operational. | 11/7/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Car emergency phone dials Kone sales. The phone shall be re-programmed to call the appropriate number in case of an emergency. | 11/7/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 11/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | The pit door shall have an electrical contact to prevent the elevator from running while the pit door is open. | 11/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | The machine room shall be kept clean. | 2/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 2/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | The pit door shall have an electrical contact to prevent the elevator from running while the pit door is open. (2nd Notice) | 3/29/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 5/29/2024 |