Inspection
Inspection Details
Equipment ID
14020
14020
Inspection Date
4/11/2018
4/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
Slide
27
27
Governor Rope Pull
250/950
250/950
Door Closing Force
25
25
External ID
Location
AT & T- Data Center
801 Chestnut, St. Louis, MO
Phone: (314) 235-9992
801 Chestnut, St. Louis, MO
Phone: (314) 235-9992
Owner
AT&T-St. Louis
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
Billing
Attn: AT&T- Elevator Management c/o Lerch Bates
4201 Northview Dr Suite 314, , MD 20716
4201 Northview Dr Suite 314, , MD 20716
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service to be tested at a later date. | 8/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light not working on battery backup | 8/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell inoperative. | 7/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative. | 2/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site. | 1/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in elevator pit is not working, needs repair | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of elevator on emergency power. | 4/20/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of elevator emergency power selector switches (2). One at guard desk, one in fire control room. | 4/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase I operations, record results. | 4/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase II operations, record results. | 4/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state elevator certificate. | 11/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Hoist ropes need to be shortened | 5/30/2025 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | The pin that supports the brake pad on the machine has moved and needs to be repaired. Red-tagged, Re-inspection required | 5/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Hoist ropes need to be shortened. Re-inspection required | 1/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in elevator pit is not working, needs repair | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |