Inspection
Inspection Details
Equipment ID
22203
22203
Inspection Date
9/12/2019
9/12/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
1"
1"
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
ffa7199c-61e9-4767-963d-a6781fb6dfea
ffa7199c-61e9-4767-963d-a6781fb6dfea
Location
The Fountains at West County Assisted Living
15826 CLAYTON RD, ELLISVILLE, MO
Phone: (000) 000-0000
15826 CLAYTON RD, ELLISVILLE, MO
Phone: (000) 000-0000
Owner
Attn: The Fountains of Ellisville
The Fountains of Ellisville
15826 Clayton Road, Ballwin, MO 63011
Phone: (636) 220-1665
Email: sues@fountainsofwestcounty.com
The Fountains of Ellisville
15826 Clayton Road, Ballwin, MO 63011
Phone: (636) 220-1665
Email: sues@fountainsofwestcounty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.3.1 | Yes | Yes | Provide complete Category 5 testing. | 9/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.26 - Broken rope, chain, or tape switch | 2.26.2.6 | Yes | Yes | The broken suspension member (belt) switches (there are 2) shall each stop the car independently. Note: Presently, both switches have to be tripped to stop the car. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Firefighters operation phase two door close button inside the fire service panel shall be functional. Note: The second door close button on the main car operating panel works, so phase 2 is operational. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work. | 10/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust up-trust/doors for proper clearance to door hanger track, but not exceeding door to sill clearance allowance. (Multiple floors) | 9/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures. Fire service log to be recorded monthly. Note: Basic MCP is present but none of the required logs for 2021, 2022, and 2023. | 9/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. Note: This violation was originally cited 9/26/23 and still not corrected. This elevator is not red tagged as the other unit at this location was already red tagged. If phone is not operational at the time of the red tag removal of the other unit at this location, this unit will be red tagged. | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. | 3/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. |