Inspection
Inspection Details
Equipment ID
13663
13663
Inspection Date
10/3/2019
10/3/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
James Dalton
James Dalton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
ef83b00e-2d0c-4b39-8f63-2ad5a646e94a
ef83b00e-2d0c-4b39-8f63-2ad5a646e94a
Location
Kiener East Garage
500 PINE ST, SAINT LOUIS, MO
Phone: (314) 241-4262
500 PINE ST, SAINT LOUIS, MO
Phone: (314) 241-4262
Owner
Inter Park Holdings LLC
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
Billing
Attn: Inter Park
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
100 S 9TH ST, SAINT LOUIS, MO 63102-1124
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Door close operation shall require constant pressure on phase 2 fire service. | 10/1/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency alarm bell shall work on battery power | 10/1/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Return to phase 1 fire service did not work when turning phase 2 switch to off. | 10/1/2018 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | A category 5 inspection is required. | 3/5/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 1 and Phase 2 key switches shall be keyed the same. | 3/5/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency lights shall work. | 1/15/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell shall work. | 3/5/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Provide code compliant machine room lighting. | 10/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Yes | No | Provide GFCI type receptacle in the machine room. | 10/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Provide a sign on the machine room door. | 10/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Remove the foreign wires passing through the machine room rear door. | 10/3/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Provide code compliant pit lighting. | 10/3/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | Yes | Phase 2 fire service shall be operational. - Elevator Red Tagged. | 8/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | Yes | The lower pit stop switch shall be operational. - Elevator Red Tagged. | 8/12/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site required documentation (including fire service log) shall be provided in the machine room. | 9/1/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/17/2026 |