Inspection
Inspection Details
Equipment ID
4667
4667
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Kauffman Stadium
103 Royal Way, Kansas City, MO
Phone: (816) 921-9000
103 Royal Way, Kansas City, MO
Phone: (816) 921-9000
Owner
Kauffman Stadium
One Royal Way, Kansas City, MO 64141
One Royal Way, Kansas City, MO 64141
Billing
Attn: Kauffman Stadium
One Royal Way, , MO 64141
One Royal Way, , MO 64141
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | replace broken deck barricade on the lower right side | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.5 | No | No | submit results of skirt index performance test | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.8 - Deck barricades and antislide devices | 8.10.4.1.1(h) | No | No | replace broken low outer deck barricade on the right side | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Submit results of skirt index test | 3/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.11.4.1 (c) | No | No | Handrails shall be kept clean of bird droppings as this is where passengers hold onto for safety | |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.11.4.1(i) | No | No | The steps shall be kept clean and free of debris such as bird droppings | |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.5 | No | No | Did not pass skirt index gap test. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.10 - Operating and safety devices | 6.1.6.3.1 Emergency Stop Buttons (Re-Inspection) | Yes | No | lower stopswitch housing is broken and being held on with tape, replace housing | 4/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | submit results of skirt index test | 4/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.9 Step/Skirt Performance Index | Yes | No | PROVIDE REQUIRED SKIRT INDEX TEST | 10/31/2024 |