Inspection
Inspection Details
Equipment ID
21711
21711
Inspection Date
10/7/2019
10/7/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
860
860
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25F/28R
25F/28R
External ID
012ff8ab-cbf4-48fd-b035-bc258db0fe1d
012ff8ab-cbf4-48fd-b035-bc258db0fe1d
Location
Gateway Science Academy - South
6651 GRAVOIS AVE, SAINT LOUIS, MO
Phone: (314) 669-9000
6651 GRAVOIS AVE, SAINT LOUIS, MO
Phone: (314) 669-9000
Owner
6651 Gravois LLC
6651 GRAVOIS AVE, SAINT LOUIS, MO 63116-1125
6651 GRAVOIS AVE, SAINT LOUIS, MO 63116-1125
Billing
Attn: 6651 Gravois LLC
6651 GRAVOIS AVE, SAINT LOUIS, MO 63116-1125
6651 GRAVOIS AVE, SAINT LOUIS, MO 63116-1125
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | 9/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | 9/4/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | The hoistway door sill grout on the outside of the "G" landing shall be repaired. | 9/4/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Adjust the "G" level hoistway door to close properly. | 9/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The category 5 full load testing shall be completed. The only item of the category 5 test that was able to be completed was the relief pressure with a full load. All other category 5 testing items remain. | 3/1/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | There were issues getting the unit to operate properly. All annual inspection items still need to be tested with the exception of the relief pressure. | 3/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A means shall be provided to collect the overflow oil from the jack head. | 9/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | There is an excessive amount of oil on the pit floor. The pit shall be kept clean and dry. | 9/4/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit lighting shall be operational. | 9/4/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | Reverse phase relay has been removed and a jumper has been installed in its place. Replace proper device. | 8/29/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 9/4/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Provide Phase 1 & 2 fire fighters instructions. | 9/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The low pressure switch does not work and shall be operational. | 8/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 8/29/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor. | 9/4/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Firefighters phase two instructions shall be posted inside the car on the car operating panel. | 9/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase one key-switch bezel shall be legible. | 9/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The illumination inside the car enclosure shall be operational. Note: One of the two lighting fixtures inside the car aren't working. | 9/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: Display certificate is expired. | 9/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car enclosure lights shall be operational. | 9/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light shall be operational. | 8/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. | 9/4/2025 |