Inspection
Inspection Details
Equipment ID
18523
18523
Inspection Date
9/30/2019
9/30/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
7685094a-e432-4b6c-b3c5-16e227365e63
7685094a-e432-4b6c-b3c5-16e227365e63
Location
First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO
Phone: (636) 239-7560
6890 HIGHWAY 100, WASHINGTON, MO
Phone: (636) 239-7560
Owner
First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
Billing
Attn: First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 9/30/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | Yes | Yes | Phase 2 fire service shall be operational. Elevator left in service and violation shall be corrected in 30 days. | 3/2/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/2/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/19/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Unit is equipped with an overspeed valve. A category 5 test is due on the overspeed valve in 2022. | 9/21/2022 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Heat detectors shall be installed within 24 inches of each sprinkler head located in the elevator machine room and shall active the shunt trip. | 9/21/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency bell and emergency light did not work when the 110V disconnect was de-energized. | 9/21/2022 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Heat detectors shall be installed within 24 inches of each sprinkler head located in the elevator machine room and shall active the shunt trip. | 11/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency bell and emergency light did not work when the 110V disconnect was de-energized. | 11/6/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/11/2026 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Jack head drain tube shall be routed to measurable containers in pit. Currently tubes are routed straight to pump unit. |