Inspection
Inspection Details
Equipment ID
15717
15717
Inspection Date
9/30/2019
9/30/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
b8afa9ca-722b-469d-a0cb-add50672c279
b8afa9ca-722b-469d-a0cb-add50672c279
Location
Pepper Lofts
707 N 1ST ST, SAINT LOUIS, MO
Phone: (000) 000-0000
707 N 1ST ST, SAINT LOUIS, MO
Phone: (000) 000-0000
Owner
Attn: Unk
Pepper Lofts
707 NORTH 1ST ST, ST. LOUIS, MO 63102
Phone: (000) 000-0000
Pepper Lofts
707 NORTH 1ST ST, ST. LOUIS, MO 63102
Phone: (000) 000-0000
Billing
Attn: Unk
Pepper Lofts
707 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: tpoole@advantesgrp.com
Pepper Lofts
707 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (000) 000-0000
Email: tpoole@advantesgrp.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | No | No | Car door restrictor does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | High voltage (110V) wiring on car top shall be enclosed in conduit. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Hoistway duct covers shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Suspension rope data tags shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump pump cover shall be installed flush with the pit floor. | 1/4/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Weight related testing of safeties, buffers, and machine brakes shall be completed. | 11/8/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door restrictor shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be posted in the machine room in a non-combustible frame. | 10/26/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | A counterweight guard shall be installed. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency light shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall operate on auxiliary power. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | Yes | Fire service phase 1 instructions shall be posted at the hall key switch, and fire service phase 2 instructions shall be posted in the car. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service phase 1 & phase 2 key switches shall be legible. | 9/22/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking and self-closing. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The machine room fire extinguisher shall be tagged to verify that the extinguisher is current. | 10/26/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Traveling cables in the machine room shall be enclosed in wireway. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be provided in the machine room. |