Inspection
Inspection Details
Equipment ID
2330
2330
Inspection Date
4/27/2018
4/27/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
Location
Housing Unit #11
3401 Faraon, St. Joseph, MO
Phone: (816) 387-2158
3401 Faraon, St. Joseph, MO
Phone: (816) 387-2158
Owner
WRDCC
3401 Faraon St, St. Joseph, MO 64506
3401 Faraon St, St. Joseph, MO 64506
Billing
Attn: WRDCC
3401 Faraon, , MO 64506
3401 Faraon, , MO 64506
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Photo eye door reopening device does not function. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Fire extinguisher in machine room has expired certification. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Provide fire service instructions inside and outside elevator. | 2/22/2023 |
| conversion | conversion | n/a | No | No | emergency car light and bell do not operate. | 2/22/2023 |
| conversion | conversion | n/a | No | No | Emergency car light and bell not working | 2/22/2023 |
| conversion | conversion | n/a | No | No | Post fire service instructions inside elevator | 2/22/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter instructions next to hall fire keyswitch. Presently has phase 2 instructions next to hall fire keyswitch. | 2/22/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not overide security for bottom floor car call. 14 days to repair or red tagged. | 8/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light does not operate. | 8/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | No emergency signal device. Emergency bell does not operate and no phone present on elevator. | 8/23/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Firefighter phase 2 operation does not override security for bottom floor car call. 14 days to repair or red tagged, may apply for variance from the state. | 9/8/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair machine room lighting. Not all machine room light fixtures illuminate | 2/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 2/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MRL not up to date | 2/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/22/2023 |