Inspection
Inspection Details
Equipment ID
7856
7856
Inspection Date
4/9/2018
4/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Sigma Chemical-Cherokee Bldg
165 Cherokee St, St. Louis, MO
Phone: (314) 771-5765
165 Cherokee St, St. Louis, MO
Phone: (314) 771-5765
Owner
Sigma Chemical
PO Box 14508, St Louis, MO 63178
PO Box 14508, St Louis, MO 63178
Billing
Attn: Sigma Chemical
3300 S Second St, , MO 63118
3300 S Second St, , MO 63118
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Close space between cab gate sections. Left side. | 4/22/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Cab stop switch inoperable. | 10/12/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase I light and buzzer inoperative. Repair within 30 days. | 10/12/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Car ceiling panels are open egg crate type, providing no protection for passengers in event of bulb breakage. Panels should be replaced with solid panels or install plastic tubes and end caps over bulbs | 6/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light & alarm shall work in event of power outage. Re-inspection required | 2/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing emergency lights to work. | 5/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Cylinder packing worn and leaking, repair as needed. | 5/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide guard on bulbs in the elevator machine room. | 5/18/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current tested fire extinguisher in the elevator machine room. | 5/18/2023 |