Inspection
Inspection Details
Equipment ID
2119
2119
Inspection Date
11/1/2019
11/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Leo
David Leo
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
UNK
UNK
External ID
58bf316c-3601-47cb-ba51-7217a4ef5c4a
58bf316c-3601-47cb-ba51-7217a4ef5c4a
Location
Authenrieth Properties
2 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 725-2414
2 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 725-2414
Owner
Attn: Authenrieth Properties
Authenrieth Properties
#2 MERAMEC AVE, CLAYTON, MO 63105
Phone: (314) 725-2414
Email: Marjorie@schlaflycorporation.com
Authenrieth Properties
#2 MERAMEC AVE, CLAYTON, MO 63105
Phone: (314) 725-2414
Email: Marjorie@schlaflycorporation.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove standing water from the elevator pit | 12/31/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair inoperative emergency phone | 8/9/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean of dirt and water. | 12/31/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Tail sheave needs to be replaced due to water damage. | 12/31/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and self locking. | 12/31/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - n/a | n/a | No | No | Water in pit needs to be removed | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Governor tension sheave shall be replaced. 1" rod holding sheave is rusted out. | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | Check integrity of pit buffers. | 12/26/2019 |
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | No | No | Check integrity of all rail bottoms (under water and large amounts of rust flaking off). 5.13 | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self closing and locking, and steps leading up to room shall be attached. | 12/26/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Steps leading up to room shall be attached. | 12/25/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | 12/25/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs repair, door hinges pulled from frame and door. | 12/25/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete - Governor must be tested for electrical and jaw speeds. Re-inspection required | 12/2/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be kept dry and clean from all water or debris. Remove all water from elevator pit. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed inside of the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A valid fire extinguisher shall be kept inside of the elevator machine room. |