Inspection
Inspection Details
Equipment ID
6525
6525
Inspection Date
10/16/2019
10/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
a8611ee9-8123-431c-834e-6700bb92435d
a8611ee9-8123-431c-834e-6700bb92435d
Location
Soll's Gateway Market
1206 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 367-0400
1206 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 367-0400
Owner
Attn: Sou's Gateway Market
Joffe, Jay
1206 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63113
Phone: (314) 367-0400
Email: sollsgateway@gmail.com
Joffe, Jay
1206 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63113
Phone: (314) 367-0400
Email: sollsgateway@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 1/22/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide a permanent means to access machine room. | 1/22/2019 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Post capacity plate and "No Passengers" signage inside elevator cab. | 1/22/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Provide a pit stop switch. | 1/22/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide code compliant pit lighting. | 1/22/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust the gate switch to prevent the car from running when the car door is open greater than 2". | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust the top floor door for proper balance. | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust the top floor door locking bar for proper operation. | 11/4/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 9/8/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the machine room shall be not less than 10 foot-candles at floor level. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install a code data plate. It shall read: "Missouri Minimums" | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/1/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The reverse phase switch is broken and requires replacement. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/1/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | The four inch electrical box located in the machine room requires a cover. | 9/1/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit of dirt and debris. | 9/1/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than 5 foot-candles at the pit floor. The fixture switch shall be provided and accessible from the pit access door. | 9/1/2021 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Each freight car enclosure shall have lighting not less than two and one-half (2.5) foot-candles. Bulbs or tubes shall be guarded to prevent breakage. | 9/1/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Counterweight guards shall extend from a point not more than 12" above the pit floor to a point not less than 7' above the pit floor. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The electrical box attached to the underside of the car needs a cover plate. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 7/16/2021 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)1 | No | No | There is structural damage under the car frame that shall be repaired. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The electrical box attached to the top of the car needs a cover plate. | 9/1/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)6 | Yes | Yes | Remove the unwired governor speed switch. Governor speed switch is not required for elevators running less than 150 fpm. - Unit not Red Tagged | 7/16/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/19/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be operational. | 9/19/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 9/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The vision panel on the first floor does not meet code. The vision panel in the basement is broken. Replace both panels to meet the following code: Ref: A17.1-2016, 2.14.2.5, A17.2, 1.11 | 9/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | Yes | This car has been red tagged. Upon arrival, the button was pushed to call the elevator, the doors opened, and the car was not at the floor. | 8/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | There is a 3 1/2" gap between the door and the wall; it should be around 1 1/4". | 8/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is complete. Need to do all of the annual, slide, pull out/pull thru, and governor switch. | 8/31/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | There is a 3 1/2" gap between the door and the wall; it should be around 1 1/4". Take corrective action. | 8/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing is incomplete. Need to do all of the annual, slide, pull out/pull thru, and governor switch. | 8/26/2024 |