Inspection
Inspection Details
Equipment ID
1254
1254
Inspection Date
4/6/2018
4/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
F 17 R 19
F 17 R 19
External ID
Location
Factory Shoppes at Branson Meadows
4600 Gretna Rd, Branson, MO
Phone: (417) 339-2580
4600 Gretna Rd, Branson, MO
Phone: (417) 339-2580
Owner
Factory Shoppes at Branson Meadows
4562 Gretna Rd, Branson, MO 65616
4562 Gretna Rd, Branson, MO 65616
Billing
Attn: Factor Shoppes at Branson Meadows
4562 Gretna Rd, , MO 65616
4562 Gretna Rd, , MO 65616
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Obtain and display a current state operating certificate in the machine room | 7/5/2018 |
| conversion | conversion | n/a | No | No | Replace the emergency light battery and bulbs. | 7/5/2018 |
| conversion | conversion | n/a | No | No | Repair the emergency phone as the line is dead | 7/5/2018 |
| conversion | conversion | n/a | No | No | Replace the burnt out light tubes in the car ceiling. | 7/5/2018 |
| conversion | conversion | n/a | No | No | Have the fire extinguisher re-certified. | 7/5/2018 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Replace the missing fire service fire hat chiclet in the COP. | 3/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 3/9/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the burnt out light bulbs in the car ceiling. | 3/9/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 5/22/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace the burnt out light tubes in the car ceiling. | 5/22/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace the bad light tubes in the machine room on the back wall | 5/22/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Replace the bad emergency phone as it will not dial out | 3/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 5/22/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the fire extinguisher re-certiified | 5/22/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replae the emergency phone ass the incoming line is dead | 3/5/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Clean up the mess inside the car | 5/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 9/12/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 9/12/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Have the emergency phone re programed to call an answering service that can take appropriate action | |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Replace the broken machine room door handle. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Have the fire extinguisher re certified | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean up the hoistway and car inside and the pit. | |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 210.2(e) | No | No | Replace the broken stop switch in the car COP. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Replace the broken phase 1 illuminated visual signal system device on the COP |