Inspection
Inspection Details
Equipment ID
13721
13721
Inspection Date
4/11/2018
4/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
Slide
61
61
Governor Rope Pull
160/820
160/820
Door Closing Force
External ID
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 235-9992
1010 Pine St, St. Louis, MO
Phone: (314) 235-9992
Owner
AT&T-St. Louis
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
Billing
Attn: AT&T- Elevator Management c/o Lerch Bates
4201 Northview Dr Suite 314, , MD 20716
4201 Northview Dr Suite 314, , MD 20716
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Fire service to be tested at a later date. | 3/22/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light inoperative, repair. | 3/28/2019 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Perform fire service operation testing. Phase I and II | 3/28/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Repair inoperative emergency light. | 2/9/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Repair inoperative emergency phone. | 2/9/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light and alarm bell do not work. | 6/1/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency lighting is not working. Re-inspection required | 11/18/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | 2 way communication is not working. Re-inspection required | 11/18/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | x | 2-way communication is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | x | Governor safety rope pull out exceeds 30" maximum allowable (68" actual pull out). Elevator Red Tagged. | 12/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | x | Emergency lighting is not working. Elevator red tagged as this violation first cited in 2022 and is still not corrected. | 12/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/3/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. Must be completed within 60 days. | 12/3/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/29/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current ABC type fire extinguisher shall be provided in the secondary machine room. | 9/29/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lighting needs to be repaired. One or more bulbs are not working. | 9/29/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency lighting is not working. | 9/29/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/29/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete; Items still needed: all weight tests, buffer tests, governor speeds, governor pullout/pull-thru, slide, fire service, door pressure, EP. | 9/29/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | Machinery, controllers, governors, disconnects shall be numbered. All governors need to be numbered. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. Remove excess debris. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Emergency exit shall be properly secured. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. No PM/callback/repair logs, or testing records for 2022-2025. | |||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Fire service shall be tested and documented monthly. No log for 2022-2025. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Replaced CO2 fire extinguisher in machine room and secondary spaces with ABC type. Multi-year violation. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lighting needs to be repaired. One or more bulbs are not working. |