Inspection
Inspection Details
Equipment ID
6419
6419
Inspection Date
11/5/2019
11/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
George Riche
George Riche
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
2ba27a83-681f-4e04-890d-f6aac5684408
2ba27a83-681f-4e04-890d-f6aac5684408
Location
Farmers Bank
123 E 3RD ST, CAMERON, MO
123 E 3RD ST, CAMERON, MO
Owner
Farmers Bank
PO BOX 567, CAMERON, MO 64429-0567
PO BOX 567, CAMERON, MO 64429-0567
Billing
Attn: Farmers Bank
PO BOX 567, CAMERON, MO 64429-0567
PO BOX 567, CAMERON, MO 64429-0567
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide type ABC fire extinguisher inside machine room next to access door. | 11/3/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing. | 11/3/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non-elevator related material from machine room. | 11/3/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from pit floor | 11/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not illuminate | 10/17/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door shall be self-locking | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 12/9/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Seal hole that penetrates hoistway wall at lobby landing. | 12/9/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove exposed non-elevator related wiring from the hoistway enclosure. | 12/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not operate | 10/11/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove non-elevator related wiring from the hoistway | 12/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire signage next to hall button fixture at each landing | 12/9/2025 |