Inspection
Inspection Details
Equipment ID
15135
15135
Inspection Date
11/8/2019
11/8/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Edward Barfield
Edward Barfield
Relief Valve Pressure
Slide
6 in
6 in
Governor Rope Pull
50/420
50/420
Door Closing Force
15
15
External ID
92489a86-60e1-4ae4-ab23-6d36df8bded4
92489a86-60e1-4ae4-ab23-6d36df8bded4
Location
Roosevelt Town Apts
711 N EUCLID AVE, SAINT LOUIS, MO
Phone: (314) 361-7330
711 N EUCLID AVE, SAINT LOUIS, MO
Phone: (314) 361-7330
Owner
NCR
2335 N BANK DR, COLUMBUS, OH 43220-5423
2335 N BANK DR, COLUMBUS, OH 43220-5423
Billing
Attn: Roosevelt Towne Apts
711 N EUCLID AVE, SAINT LOUIS, MO 63108-1632
711 N EUCLID AVE, SAINT LOUIS, MO 63108-1632
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Need Phase II fire service instructions in car | 5/29/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Replace hoistway door rollers on floors 3,4 and 6. (Worn) | 5/29/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell and emergency light don't work in car. | 4/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Bulbs and tubes shall be guarded to prevent breakage | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide Phase II Fire Service Instructions on Car Operating Panel | 8/16/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Replace missing door closer spring on Second Landing hall door | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is inoperable. When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 1/5/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 7/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs to be serviced or replaced. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean down the hoistway. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Hoistway sill door closer, first floor, missing rod and spring. Repair or replace as needed. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Car emergency lights only one bulb working-2 required. |