Inspection
Inspection Details
Equipment ID
22155
22155
Inspection Date
10/10/2019
10/10/2019
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Joseph Ottoline
Joseph Ottoline
Relief Valve Pressure
Slide
9"
9"
Governor Rope Pull
50/1000
50/1000
Door Closing Force
18
18
External ID
d16364fc-8f4a-4885-baa4-aae9252a4ccf
d16364fc-8f4a-4885-baa4-aae9252a4ccf
Location
Old Federal Courthouse
339 BROADWAY ST, CAPE GIRARDEAU, MO
Phone: (573) 576-1306
339 BROADWAY ST, CAPE GIRARDEAU, MO
Phone: (573) 576-1306
Owner
Attn: UNK
APG Limited, LLC
PO BOX 2132, CAPE GIRARDEAU, MO 63702
Phone: (573) 207-4288
Email: linsey@rentathena.com
APG Limited, LLC
PO BOX 2132, CAPE GIRARDEAU, MO 63702
Phone: (573) 207-4288
Email: linsey@rentathena.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 8.11.2.1.1(n) | Yes | No | Replace the missing low cab ventilation trim on (2) walls. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Remove all foreign wires and cables passing through the elevator machine room. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal all machine room penetrations. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Remove wire mesh window and enclose hole. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Steam heater in machine room, if working repair to prevent leaking. If not in use, remove. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Confirm climate control in elevator machine room. Heat & A/C. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide code compliant machine room lighting of 19fc. Currently measured at 3.7fc. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car car emergency telephone shall work with 24/7 support. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | Yes | No | 2.10.2 Provide toe board on car top. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Provide a sump pump in the pit. Test the sump pump once installed. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Seal all penetrations in the hoistway. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide a counterweight runby sign in the pit. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | 2.19 - Provide unintended movement test. | 11/8/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.10.2.2.2(cc)(1) | Yes | No | Provide ascending car overspeed test. | 11/8/2019 |