Inspection
Inspection Details
Equipment ID
12593
12593
Inspection Date
10/30/2019
10/30/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
4c98640d-b5e9-4d57-bb99-d9c500099dff
4c98640d-b5e9-4d57-bb99-d9c500099dff
Location
West County Center
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
Owner
Attn: Mike Baker
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State certificate in machine room | 7/25/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 7/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone. | 7/8/2019 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | There is an 1 1/8" gap between the cop and the car door. Needs to be fixed. Reinspect. | 7/25/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Light needs to work in the pit. | 7/8/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 10/30/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 7/25/2019 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | No | The gap between elevator cab and car door are over 3/8" when the door is in the closed position. | 9/22/2020 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean elevator car top. | 9/22/2020 |
| A17.1-1996 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 1001.2(c)(19) | No | No | Toe guard is hitting the landing sill guard in elevator pit. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Car directional arrows, missing lens-provide. | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not provide 2 way communication, needs repaired. Re-inspection required | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Provide missing directional arrow lens | 3/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit is not working properly at the time of inspection. |