Inspection
Inspection Details
Equipment ID
7463
7463
Inspection Date
11/4/2019
11/4/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
a75c2ccf-d2b5-47f3-83f3-4efab8d30df3
a75c2ccf-d2b5-47f3-83f3-4efab8d30df3
Location
Holiday Inn / St. Louis Airport
4505 WOODSON RD, SAINT LOUIS, MO
Phone: (314) 427-4700
4505 WOODSON RD, SAINT LOUIS, MO
Phone: (314) 427-4700
Owner
Attn: Holiday Inn Airport
McMahon Family LP
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
McMahon Family LP
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Billing
Attn: McMahon Family LP
Brian McMahon
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Brian McMahon
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Emergency light and alarm bell not working. | 5/26/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency lights and bell do not work. | 3/9/2021 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Provide Phase I operating procedures need to be posted near key switch in lobby. | 5/28/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase II operation failed. Did not red tag - Repair required by 6/16/20 or will be taken out of service. | 3/9/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Remove all non-elevator equipment from machine room. | 5/28/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Provide guard on car bulbs. | 5/28/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | Label all relays on controller. | 5/28/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide missing oil loss log. | 5/28/2025 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove water from pit. | 5/28/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the elevator machine room | 11/1/2023 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Phase II does not keep door in open position. Repair shall be made and re-inspected within 30 days | 11/16/2022 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | No audible sound when elevator is on Phase I. Re-inspection required | 11/16/2022 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Existing phone works, but has bad microphone. Repair/replace as needed. | 1/30/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Remove fluid from the pit.(water) | 5/28/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 5/28/2025 | ||
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Car door restrictor does not work between the bottom and 2nd landing, needs repaired. Re-inspection required | 6/17/2025 |