Inspection
Inspection Details
Equipment ID
2881
2881
Inspection Date
11/5/2019
11/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
External ID
4951c9f4-4ea4-4b57-9c4d-e3a3d5205c4d
4951c9f4-4ea4-4b57-9c4d-e3a3d5205c4d
Location
Upton Pump Station
7400 REILLY AVE, ST. LOUIS, MO
Phone: (314) 638-5047
7400 REILLY AVE, ST. LOUIS, MO
Phone: (314) 638-5047
Owner
Metropolitan Sewer District STL
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Billing
Attn: Metropolitan Sewer District
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install guard on floriscent lights in car | 9/26/2019 |
| conversion | conversion | n/a | No | No | Post current state certificate in machine room space | 9/26/2019 |
| conversion | conversion | n/a | No | No | Repair alarm bell in car | 9/26/2019 |
| Missouri Minimum : Manlifts | (V) - Existing Manlifts | (V)1 | No | Yes | Put red tag on lift. No active phone line. | 4/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The original access door on the controller was removed or misplaced and replaced with a combustible door .Controller Access panel must be made of a non combustible material | 8/6/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks | 8/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The Current operating certificate shall be posted in the machine room in a non combustible frame | 8/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements. | 8/6/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | The car safeties shall be capable of stopping the rated load of the car. | 9/15/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Doors shall be equipped with an interlocks. | 10/9/2020 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Brake shall stop and hold car with 125% rated load. Unit red tagged until repaired. | 10/9/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Doors shall be equipped with an interlock. Red tagged unit. |