Inspection
Inspection Details
Equipment ID
19292
19292
Inspection Date
4/30/2018
4/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
Location
River Roads Manor
2380 Grand River Rd, Jennings, MO
Phone: (314) 867-6256
2380 Grand River Rd, Jennings, MO
Phone: (314) 867-6256
Owner
Pyramid Properties
900 Olive Street Ste 600, St. Louis, MO 63101
900 Olive Street Ste 600, St. Louis, MO 63101
Billing
Attn: River Roads Manor
2380 Grand River Road, , MO 63136
2380 Grand River Road, , MO 63136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 4/12/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Perform the required OSV testing within 90 days | 9/20/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Ceiling panels in car are open egg crate type. Providing no protection for passengers in event of light bulb breakage. Replace with solid type panels or install plastic tubes and end caps on bulbs. | 9/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | battery lowering device shall work. Repair/replace same | 9/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | battery lowering device shall work. Repair/replace same | 9/14/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Auxiliary battery lowering device (emergency rescue unit) does not work, needs repaired. Re-inspection required | 4/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The battery back–up lowering device has been removed cannot operate as designed. Reinstall the unit to operate. Reinspection required. | 4/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor is not operational. Re-inspection required |