Inspection
Inspection Details
Equipment ID
22278
22278
Inspection Date
11/15/2019
11/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Barnhart
Michael Barnhart
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
9030d0d0-c526-4d20-9278-df6c24f00fa2
9030d0d0-c526-4d20-9278-df6c24f00fa2
Location
Residences @New Longview Apt
3311 SW KESSLER DR, LEES SUMMIT, MO
Phone: (913) 422-5555
3311 SW KESSLER DR, LEES SUMMIT, MO
Phone: (913) 422-5555
Owner
NorthPoint Development
5015 NW CANAL ST STE 200, RIVERSIDE, MO 64150-7203
5015 NW CANAL ST STE 200, RIVERSIDE, MO 64150-7203
Billing
Attn: Residences @ New Longview Apt.
3301 SW KESSLER DR, LEES SUMMIT, MO 64081-2268
3301 SW KESSLER DR, LEES SUMMIT, MO 64081-2268
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | repair door restrictor | 8/17/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Repair door restrictor, it is missing parts | 11/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | maintain dry pit, standing water in the pit at the time of the inspection | 4/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post log in the machine room. | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.1 - Top-of-car stop switch | 8.11.2.1.3(a) | No | No | the car top stop switch on the control station is missing, the stop switch on the pendant station works | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | clean the pit, oil and water mixture, pistons are starting to rust | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | the door restrictor is missing parts so that it will not work | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab light bulb, only has one working light bulb | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | the monthly fie service test log in the machine room needs to be filled out monthly | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post copy of the state operating certificate in the machine room | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out cab ceiling light, required to have at least two working light bulbs | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | repair the door restrictor, the hook is on the car top | 11/9/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year | 6/13/2023 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.11.3.1.1(e) | No | No | only one of the cab ceiling lights is working, required to have two working light bulbs | 6/13/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | sump pump is plugged into the GFCI outlet, it is to be plugged into the non GFCI outlet | 6/13/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | water, oil, black mold mixture on the pit floor needs to be cleaned up | 6/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the elevator machine room expired in 2018, update with a copy of the current certificate annually | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | replace burnt out light bulb in cab ceiling light fixture, required to have at least two working light bulbs | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | clean the pit, looks like there is mold growing on the pit floor | 6/2/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | Replace car top light fixture, the fixture is broken in a way that it will not take a light bulb (2.14.7.1.4) | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | No | No | Replace missing/broken trim ring on the car operating panel (2.14.1.2.4) | 7/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate in the machine room expired in 2022, update with a new copy of the certificate annually | 12/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Heat detector in the pit is not to hang by the wires, mount detector to the wall box | 12/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | Heat detector in the pit is not to hang by the wires, mount detector to the wall box | 10/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | No | No | Pit has standing water and oil mixture on pit floor, clean pit, maintain dry pit (2.2.2.3) | 10/28/2025 |