Inspection
Inspection Details
Equipment ID
22423
22423
Inspection Date
11/26/2019
11/26/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Charles Brinkman
Charles Brinkman
Mechanic Name
Perry Nolker
Perry Nolker
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
488f32a3-c282-4f11-a877-27f36cb0f919
488f32a3-c282-4f11-a877-27f36cb0f919
Location
U-Haul
418 S TUCKER BLVD, SAINT LOUIS, MO
Phone: (618) 210-3727
418 S TUCKER BLVD, SAINT LOUIS, MO
Phone: (618) 210-3727
Owner
Attn: Ray Reome
U-Haul Moving & Storage of Downtown St. Louis
418 S. Tucker Blvd, Saint Louis, MO 63102
Phone: (314) 766-4009
Email: ray_reome@uhaul.com
U-Haul Moving & Storage of Downtown St. Louis
418 S. Tucker Blvd, Saint Louis, MO 63102
Phone: (314) 766-4009
Email: ray_reome@uhaul.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | 1) Installation of electrical equipment and wiring shall conform to NFPA 70. All raceway covers shall be installed. 4 by 4 box for camera wires needs cover. | 10/23/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | 1) Where spring buffers or solid bumpers are used, the bottom runby shall be not less than 6 in. Ref: 2.4.2.2 | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | 2) The fire extinguisher should be tagged to indicate monthly check and required annual maintenance. Rer: 8.6.1.6.5 Tag has expired. | 11/26/2019 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | 1) On site maintenance records shall be keep in accordance with the MCP. Ref: 8.6.1.4.1 | 9/11/2020 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(i) | No | No | 2) The air conditioning isn't operating correctly and could cause improper functioning of the elevator. Ref: 8.11.2.1.2(i) | 9/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is overdo for annual maintenance, need to perform maintenance. | 8/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/6/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection is required | 8/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is overdue for annual maintenance, perform maintenance | 8/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/6/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection is required 2nd notice, a third notice will result in elevator being Red-tagged and removed from service | 8/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | Counterweight derailment device does not appear to be working, needs repaired. Re-inspection required | 8/6/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. Re-inspection is required, |