Inspection
Inspection Details
Equipment ID
134
134
Inspection Date
11/21/2019
11/21/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
dce5cd29-d473-4402-897d-aa61a1d70d87
dce5cd29-d473-4402-897d-aa61a1d70d87
Location
AUM Hospitality
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 427-7600
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 427-7600
Owner
Airport Inn St Louis Airport
2401 E DIVISION ST, NATIONAL CITY, CA 91950-1901
2401 E DIVISION ST, NATIONAL CITY, CA 91950-1901
Billing
Attn: Airport Inn St Louis Airport
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3110
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Emergency phone shall work. | 5/22/2018 | |
| conversion | conversion | conversion - reinspect | x | Phone in cab still does not work | 11/6/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Current maintenance records are required in machine room. | 4/29/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Pit is to be kept clean and dry. | 4/29/2020 | ||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | OSV is not sealed and must have a cat 5 weight test performed within 90 days or less | 2/19/2026 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No MCP located in machine room | 2/19/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room for each unit | 2/19/2026 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | OSV is not sealed and is due for a full load test & tripping speed checked. Re-inspection required | 6/8/2023 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work on battery backup, needs repair. Re-inspection required | 6/8/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Means of two-way communication are inoperable and shall be repaired or replaced. | 2/19/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | x | Auxiliary lighting is inoperable and shall be repaired or replaced. | 2/19/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | x | Phone failed to operate would not dial out. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency bell failed to operate. | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current state operating certificate | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | x | OSV needs testing | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No MCP on site | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room. |