Inspection
Inspection Details
Equipment ID
17417
17417
Inspection Date
4/17/2018
4/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
470
470
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
17417
17417
Location
Boeing Bldg #75
5621 JS McDonnell Blvd, Berkeley, MO
Phone: (314) 234-6485
5621 JS McDonnell Blvd, Berkeley, MO
Phone: (314) 234-6485
Owner
Boeing Co
MC-S221-1400 PO Box 516, St Louis, MO 63166-0516
MC-S221-1400 PO Box 516, St Louis, MO 63166-0516
Billing
Attn: Boeing Co
PO Box 516 MC S221-1400, , MO 63166-0516
PO Box 516 MC S221-1400, , MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | emergency phone not working | 11/27/2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Need testing procedures in the MCP on or before 1/1/22 | 11/14/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Need oil collection container in pit, not to exceed 5 gallon capacity | 11/14/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | Full load overspeed valve test past due 90 max to complete | 11/19/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 11/14/2025 | ||
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | Test overspeed valve | 7/15/2025 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/14/2025 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Auxiliary power lowering operation is not functional. | 11/14/2025 | |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | x | Overspeed valve is not sealed or tagged. 5 year test with full load shall be performed. (2nd Notice) | 11/14/2025 | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Auxiliary power lowering operation is not functional. | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | Need testing procedures in the MCP on or before 1/1/22 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Need oil collection container in pit, not to exceed 5 gallon capacity | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |