Inspection
Inspection Details
Equipment ID
8684
8684
Inspection Date
11/12/2019
11/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
22763e84-1d42-44bf-aae0-d242322904d6
22763e84-1d42-44bf-aae0-d242322904d6
Location
Cambridge Court Condos
929 CLAYTONBROOK DR, BALLWIN, MO
Phone: (636) 227-0012
929 CLAYTONBROOK DR, BALLWIN, MO
Phone: (636) 227-0012
Owner
Attn: Baumann Property Co
Baumann Property Co
9630 Gravois Rd, St. Louis, MO 63123
Phone: (000) 000-0000
Email: kroach2009@outlook.com
Baumann Property Co
9630 Gravois Rd, St. Louis, MO 63123
Phone: (000) 000-0000
Email: kroach2009@outlook.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall work with 24/7 support. | 11/12/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. | 9/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. Jack head is 1972 Otis "Cast Head" and no documentation has been provided. Corrective action shall be taken immediately. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing & self-locking. | 8/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the machine room, convenient to the access door. | 8/1/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Clean the pit of debris, mud, etc. Remove rust from pit equipment, repair/replace as needed. Apply rust preventative treatment to all pit steel. Pit shall be kept clean and dry, investigate/repair water leak. | 8/1/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Yes | No | Remove trash and old parts (old motor, starter contacts, etc.) from the machine room/floor. | 8/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Possible single bottom jack. If the installation is determined to be a single bottom type, the jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. Documentation shall be kept on-site at all time and shall be provided to the state. No documentation provided in the machine room. Jack head is 1972 Otis Cast Head. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing & self-locking. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | A current tested & tagged ABC type fire extinguisher shall be provided in the machine room, convenient to the access door. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Clean the pit of debris, mud, etc. Remove rust from pit equipment, repair/replace as needed. Apply rust preventative treatment to all pit steel. Pit shall be kept clean and dry, investigate/repair water leak. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Yes | No | Remove trash and old parts (old motor, starter contacts, etc.) from the machine room/floor. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Cab lighting breaker not labeled and could not be found by mechanic. Location info shall be labeled in machine room (lighting tested by alternate means). |