Inspection
Inspection Details
Equipment ID
8686
8686
Inspection Date
11/12/2019
11/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
51e3c28b-622e-4102-b4fc-008b75bfe01d
51e3c28b-622e-4102-b4fc-008b75bfe01d
Location
Cambridge Court Condos
974 CLAYTONBROOK DR, BALLWIN, MO
Phone: (636) 227-0012
974 CLAYTONBROOK DR, BALLWIN, MO
Phone: (636) 227-0012
Owner
Attn: Baumann Property Co
Baumann Property Co
9630 Gravois Rd, St. Louis, MO 63123
Phone: (000) 000-0000
Email: kroach2009@outlook.com
Baumann Property Co
9630 Gravois Rd, St. Louis, MO 63123
Phone: (000) 000-0000
Email: kroach2009@outlook.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Per the MO AHJ, this elevator has been confirmed to have a single bottom jack. The jack shall be replaced or have a governor with safeties installed or a plunger gripper installed. If the jack is replaced, documentation shall be available on-site at all time and shall be provided to the state. | 9/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. | 9/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 9/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. | 9/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. Pit has 4 to 6 inches of water in it. | 9/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Yes | No | The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned. | 8/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. (Multi-year violation) | 8/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. (Multi-year violation) | 8/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, and evacuation procedures. Fire service log to be recorded monthly. | 5/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit sump pump not working. Repair or replace as needed. | 8/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Clean the pit. Remove rust from pit equipment, repair/replace as needed. Apply rust preventative treatment to all pit steel. Pit shall be kept clean and dry, investigate/repair water leak. | 8/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing & self-locking. | 8/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 5/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit sump not working. Repair/replace as needed. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 5/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit shall be kept dry. Clean pit; remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel. Pit shall be kept dry, investigate/repair source of water leak. Pit has 4-6" of water/oil. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 5/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. All violations are repeat violations from previous years and the AHJ requires that all violations must be re-inspected. | 5/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Elevator is equipped with an overspeed valve and category 5 testing is due on or before the next annual inspection. | 5/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | > 2.8.2 Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit shall be kept dry. Clean Pit. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel. Pit shall be kept dry investigate/repair water leak Pit has 4-6" water/oil. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be self-closing and self-locking. |