Inspection
Inspection Details
Equipment ID
10942
10942
Inspection Date
11/8/2019
11/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
650
650
Slide
Governor Rope Pull
Door Closing Force
20F/23R
20F/23R
External ID
e80f7864-ba7e-4771-8f5c-c5dab4d47873
e80f7864-ba7e-4771-8f5c-c5dab4d47873
Location
Elsberry School
188 TOMAHAWK DR, ELSBERRY, MO
Phone: (573) 898-5554
188 TOMAHAWK DR, ELSBERRY, MO
Phone: (573) 898-5554
Owner
Attn: Anne
Lincoln County R-2 School District
PO BOX 106, ELSBERRY, MO 63343
Phone: (573) 898-5554
Email: amoe@elsberry.k12.mo.us
Lincoln County R-2 School District
PO BOX 106, ELSBERRY, MO 63343
Phone: (573) 898-5554
Email: amoe@elsberry.k12.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 12/27/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean and dry. Remove water from the pit floor. | 12/27/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an unsealed overspeed valve and shall have a category 5 test performed in 2022. The overspeed valve shall be tagged and sealed after a successful test. | 12/12/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. Pit steel starting to delaminate. | 12/18/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 12/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Permanently mounted pressure gauge shall be replaced with properly calibrated gauge or pressure fitting. | 12/18/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP fire service testing must be properly documented monthlty on log sheet. | 12/18/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in machine room in a non-cumbustible frame. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP fire service log must be documented monthly on log sheet. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Car emergency lighting shall work. | |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | All passenger elevator car floors shall be maintained so that persons are not exposed to the hazard of the tripping or falling. |