Inspection
Inspection Details
Equipment ID
20054
20054
Inspection Date
11/27/2019
11/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
bb3d173b-a610-457c-9732-ce8c944d6e53
bb3d173b-a610-457c-9732-ce8c944d6e53
Location
MO Western Remington Hall
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 383-7143
4525 DOWNS DR, SAINT JOSEPH, MO
Phone: (816) 383-7143
Owner
Attn: MO Western State University
MO Western State University
4525 DOWNS DR, SAINT JOSEPH, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
MO Western State University
4525 DOWNS DR, SAINT JOSEPH, MO 64507
Phone: (816) 271-4417
Email: phyplant@missouriwestern.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not operate. | 11/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate. | 11/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine room | 5/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not operate | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity. | 5/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | No | No | Identify the inside of hoistway doors with a numeral | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Identify controller as #2 | 4/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | Yes | No | Hall and car firefighter keyswitches shall be operable by the FEO-K1 key. Existing elevator in the same building uses the FEO-K1 key. | 11/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone does not operate | 11/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | auxiliary lowering unit does not operate | 11/26/2024 |