MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Elevator pit sump pump discharge line is broken, may have been hit by bottom of elevator cab, needs repaired.
|
1/5/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake
|
Yes
|
Yes
|
The rope gripping device that is installed on this unit to conform for unintentional movement of the elevator car is not activating. The device shall be repaired or replaced and a reinspection is required. If the device is replaced an alteration permit and inspection is required.
|
8/30/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required.
|
8/30/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
No
|
No
|
Multiple missing electrical duct covers are missing in the machine room and shall be reinstalled.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
No
|
No
|
Multiple missing electrical duct covers are missing in the machine room and shall be reinstalled.
|
|