Inspection
Inspection Details
Equipment ID
10540
10540
Inspection Date
4/19/2018
4/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
James House
4310 St. Ferdinand, St. Louis, MO
Phone: (314) 652-8997
4310 St. Ferdinand, St. Louis, MO
Phone: (314) 652-8997
Owner
St Louis Housing Authority
3520 Page Blvd, St Louis, MO 63106
3520 Page Blvd, St Louis, MO 63106
Billing
Attn: St Louis Housing Authority
3520 Page Blvd, , MO 63106
3520 Page Blvd, , MO 63106
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Plunger for restricted opening missing replace | 2/13/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase II door open inoperative repair | 5/24/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light inoperative | 5/24/2019 |
| conversion | conversion | n/a | No | No | Clean pit | 2/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Reinspection of the emergency phone and it did not work. Reinspect when repaired | 9/23/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor does not work, needs repair. Re-inspection required | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Replace damaged rollers on counterweight | 4/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cotter pins are missing on counterweight tie rods. Repair | 4/9/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Phone line problem | 4/9/2024 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Counterweight runby is 0 inches. Shorten hoisting cables to provide 6 inches of counterweight runby. Re-inspection required | 6/27/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | Need to clean debris from elevator pit. Re-inspection required | 6/27/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 7/31/2025 |