Inspection
Inspection Details
Equipment ID
10715
10715
Inspection Date
12/4/2019
12/4/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Craig Maupin
Craig Maupin
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
24/26
24/26
External ID
bfc4684f-4b5c-4b38-9e47-5b72a23f4818
bfc4684f-4b5c-4b38-9e47-5b72a23f4818
Location
Argyle Parking Garage
225 N EUCLID AVE, SAINT LOUIS, MO
Phone: (314) 589-6023
225 N EUCLID AVE, SAINT LOUIS, MO
Phone: (314) 589-6023
Owner
St. Louis City Treasurer
133 S 11TH ST STE 520, SAINT LOUIS, MO 63102-1135
133 S 11TH ST STE 520, SAINT LOUIS, MO 63102-1135
Billing
Attn: Kiel Parking Facility
133 S 11TH ST STE 530, SAINT LOUIS, MO 63102-1135
133 S 11TH ST STE 530, SAINT LOUIS, MO 63102-1135
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Cab keyed stop switch not overridden on Phase I return, repair. | 11/20/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 3/14/2024 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.11.3.1.3(b) | No | No | The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. | 3/14/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work correctly. | 8/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. | 8/4/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors, does not catch at bottom landing. | 11/12/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | 6x6 electrical box in machine room needs to have wiring inside box and cover installed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |