Inspection
Inspection Details
Equipment ID
5625
5625
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
Sunrise Assisted Living
1880 Clarkson Rd, Chesterfield, MO
Phone: (636) 536-3800
1880 Clarkson Rd, Chesterfield, MO
Phone: (636) 536-3800
Owner
Sunrise Assisted Living
1880 Clarkson Rd, Chesterfield, MO 63017
1880 Clarkson Rd, Chesterfield, MO 63017
Billing
Attn: Sunrise Assisted Living
1880 Clarkson Rd., , MO 63017
1880 Clarkson Rd., , MO 63017
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Door will not stay open on Phase II operation | 7/11/2018 |
| conversion | conversion | n/a | No | No | Repair door Restrictor | 7/11/2018 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 6/22/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work properly. Agent said it sounded "extremely faint" and inspector had to repeat everything multiple times to be understood. | 1/17/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. There are parts missing. | 1/17/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 1/4/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 1/4/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/4/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Elevator car door restrictor does not work, parts are missing, need to repair car door restrictor. Re-inspection required | 7/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperable. Re-inspection required | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency battery lowering is not operational. Re-inspection required |