Inspection
Inspection Details
Equipment ID
8284
8284
Inspection Date
5/4/2018
5/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
Location
Crest Medical Bldg
10000 Watson Rd, Ste L5, Crestwood, MO
Phone: (314) 822-1790
10000 Watson Rd, Ste L5, Crestwood, MO
Phone: (314) 822-1790
Owner
Jerome Goldenburg
10000 Watson Rd, Suite 1-L-5, Crestwood, MO 63126-1844
10000 Watson Rd, Suite 1-L-5, Crestwood, MO 63126-1844
Billing
Attn: Crest Medical Building, JV
10000 Watson Rd, Suite 1-L-5, , MO 63126-1844
10000 Watson Rd, Suite 1-L-5, , MO 63126-1844
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Category 1 relief valve pressure was not tested. | 7/13/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Make the emergency light operational. | 6/21/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency bell shall be operational when 110v source is removed. | 6/5/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/5/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without use of a key. | 5/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 5/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 5/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 5/30/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. The diagrams in the machine room are not correct. | 10/1/2024 |